Eaton UPS with SNMP not changing to LB ups.status on low battery #2619
Labels
Eaton
FreeBSD
issues related to FreeBSD and its derivatives (including pfSense)
impacts-release-2.8.2
Issues reported against NUT release 2.8.2 (maybe vanilla or with minor packaging tweaks)
Incorrect or missing readings
On some devices driver-reported values are systemically off (e.g. x10, x0.1, const+Value, etc.)
SNMP
Milestone
When the low battery warning is triggered the ups.status doesn't update to LB and stays on OB, DISCHRG. The warning is triggered and is visible through the Eaton Network-M3 web UI, but the status is never updated for NUT. I have tested with low the warning trigger at 5% with 0 runtime and 5% with 300 runtime with the same results.
Since the ups.status isn't set to LB status the shutdown is never triggered.
OS: pfSense 24.03-RELEASE
Nut Version: 2.8.2
UPS: Eaton 5PX 3000 RT2U G2 - 1.10.0019
Network Card: Eaton Network-M3 - 1.0.4
Driver: SNMPv3